Brand: Baldor
SKU: FPM2562T-2/4
Baldor FPM2562T-2/4, Fire Pump Motor, 200 HP, 200/400 Volts, 266 Amps, 3 Phase, 60 Hz, 3565 RPM, OPEN Enclosure, 444TS Frame, Standard, A44048M Motor Type, Iron Frame
Fire Pump motor is for use on fire pumps installed per NFPA-20. All motors meet UL requirements in open enclosures designed for relatively clean and dry environments.
Features
- UL File E481231
- 50/60 Hertz
- 200/400V, 230/460V, 460V
- Rolled Steel and Cast Iron Frames
- Exterior Red Paint RAL3002
- Class F Insulation system
- 1.15 Service Factor, 40° C ambient continuous
Applications
- Fire Suppression
- Fire Pumps installed per NFPA-20
Note: Picture is illustrative and may not reflect the actual product
Key Features:
Description
Fire Pump motor is for use on fire pumps installed per NFPA-20. All motors meet UL requirements in open enclosures designed for relatively clean and dry environments.
Features
- UL File E481231
- 50/60 Hertz
- 200/400V, 230/460V, 460V
- Rolled Steel and Cast Iron Frames
- Exterior Red Paint RAL3002
- Class F Insulation system
- 1.15 Service Factor, 40° C ambient continuous
Applications
- Fire Suppression
- Fire Pumps installed per NFPA-20
Note: Picture is illustrative and may not reflect the actual product
Specifications
| Brand | Baldor |
| Mfg. Number | FPM2562T-2/4 |
| Product Type | Fire Pump Motor |
| Horsepower | 200 HP |
| Voltage | 200/400 Volts |
| Phase | 3 |
| Frequency | 60 Hz |
| Synchronous Speed | 3600 RPM |
| Speed | 3565 RPM |
| Speed Code | Single Speed |
| High Voltage Full Load Amps, mps | 266 Amps |
| Enclosure | OPEN |
| Frame Size | 444TS |
| Motor Type | A44048M |
| Motor Standards | NEMA |
| Number of Poles | 2 |
| Pulley Face Code | Standard |
| Frame Material | Iron |
| Motor Lead Quantity/Wire Size | 12 @ 2 AWG |
| Overall Length | 35.88 in |
| Service Factor | 1.15 |
| Efficiency @ 100% Load | 94.50% |
| Duty Rating | CONT |
| Inverter Code | Not inverter |
| Mounting Type | Foot |
| Auxillary Box | No |
| Base Indicator | Rigid |
| Bearing Grease Type | POLYREX EM (-20F +300F) |
| Current | 532.0 A @ 200 V 266.0 A @ 400 V |
| Design Code | B |
| Drip Cover | No Drip Cover |
| Heater Indicator | No heater |
| KVA Code | F |
| Motor Lead Exit | KO Box |
| Motor Lead Termination | Flying Leads |
| Rodent Screen | No |
| Shaft Diameter | 2.375 in |
| Insulation Class | F |
| Power Factor | 85 |
| Pulley End Bearing Type | Ball Bearing |
| Shaft Extension Location | Pulley End |
| Shaft Rotation | Reversible |
| Shaft Slinger Indicator | No Slinger |
| Starting Method | Wye Start - Delta Run |
| Vibration Sensor Indicator | No Vibration Sensor |
| Thermal Device - Bearing | No |
| Thermal Device - Winding | No |
| Ambient Temperature | 40 °C |
| Agency Approvals | CCSA, US CSA, EEV, UL |